Transformers

Explain how a transformer works by mutual induction, derive V_s/V_p = N_s/N_p and I_s/I_p = N_p/N_s for an ideal transformer, describe energy losses, and explain the role of transformers in power transmission.

If something looks wrong, please tell us.

By the end of this lesson you can

  • Describe the construction of a transformer.
  • Derive the voltage and current ratios for an ideal transformer, stating the assumptions.
  • Distinguish step-up and step-down transformers.
  • List the sources of energy loss and how each is reduced, and explain high-voltage transmission.

Power stations generate electricity at one voltage, transmission lines carry it at a far higher voltage, and our homes use a much lower one. The device that changes ac voltages with very little loss is the transformer, which works by mutual induction.

Construction

A transformer has two coils insulated from each other, wound on a soft-iron core - either one on top of the other or on separate limbs of the core. The primary coil (N_p turns) is usually the input; the secondary coil (N_s turns) is the output. An alternating current in the primary produces an alternating flux in the core, which links the secondary and induces an emf in it.

The ideal transformer

  1. Let φ be the flux in each turn of the core. The emf induced in the secondary is ε_s = −N_s dφ/dt.
  2. The same changing flux induces a back emf in the primary: ε_p = −N_p dφ/dt.
  3. If the primary has negligible resistance, ε_p equals the applied voltage v_p (otherwise the primary current would be infinite).
  4. If the secondary current is small, v_s ≈ ε_s.
  5. Dividing: v_s/v_p = N_s/N_p.
  6. If no energy is lost, input power = output power: i_p v_p = i_s v_s.

Ideal transformer: V_s/V_p = N_s/N_p and I_s/I_p = N_p/N_s (rms or peak values; the frequency is unchanged).

The derivation assumes small primary resistance and current, the same flux in both coils (little leakage from the core), and small secondary current. A well designed real transformer can exceed 95% efficiency, so the ideal relations are good approximations.

Step-up and step-down transformers

  • Step-up (N_s > N_p)
    • V_s > V_p
    • I_s < I_p
    • Used at power stations before transmission
  • Step-down (N_s < N_p)
    • V_s < V_p
    • I_s > I_p
    • Used at sub-stations and for chargers and appliances

A step-up transformer does not create energy: it raises the voltage but lowers the current in the same proportion, so the power stays (ideally) the same.

Energy losses in real transformers

Losses in a transformer
LossCauseHow it is reduced
Flux leakageSome primary flux does not pass through the secondary (poor core design, air gaps)Wind the primary and secondary one over the other
Resistance of windingsI²R heating in the wiresUse thick wire for high-current, low-voltage windings
Eddy currentsThe alternating flux induces circulating currents in the iron core, heating itUse a laminated core
HysteresisRepeated reversal of the core's magnetisation dissipates energy as heatUse a core material with low hysteresis loss

Transformers and power transmission

At a power station the generator's voltage is stepped up, so the current in the long transmission lines is small and the I²R loss is cut down. Near the consumers it is stepped down at an area sub-station, then further at distribution sub-stations and on utility poles, before reaching homes at the rated domestic voltage.

From power station to home

  1. Generator Produces ac at a moderate voltage.
  2. Step-up transformer Raises the voltage greatly; current falls.
  3. Transmission lines Long distance at high voltage, low current, small I²R loss.
  4. Step-down sub-stations Voltage lowered in stages.
  5. Home supply Delivered at a safe, usable voltage.

Worked example 1: a step-down transformer

A transformer steps 230 V down to 11.5 V. Its primary has 2000 turns. N_s = N_p × V_s/V_p = 2000 × 11.5 ÷ 230 = 100 turns. If the secondary supplies 2 A to a device, an ideal transformer draws I_p = I_s × N_s/N_p = 2 × 100 ÷ 2000 = 0.1 A from the mains. Check: 230 × 0.1 = 23 W = 11.5 × 2.

Worked example 2: efficiency

A transformer takes 2.0 A at 230 V from the mains and delivers 8.0 A at 52 V. Input power = 460 W; output power = 416 W. Efficiency = 416 ÷ 460 × 100% ≈ 90%; the remaining 44 W is lost as heat in the windings and core.

Worked example 3: why step up?

A town needs 1 MW through lines of total resistance 5 Ω. At 11 kV, I = 10⁶ ÷ 11 000 ≈ 91 A and the line loss is 91² × 5 ≈ 41 kW. Stepped up to 220 kV (a ratio of 20), I ≈ 4.5 A and the loss is about 4.5² × 5 ≈ 0.1 kW - roughly 400 (= 20²) times smaller.

Key takeaways

  • A transformer works by mutual induction through a shared iron core; it works only with ac.
  • Ideal: V_s/V_p = N_s/N_p, I_s/I_p = N_p/N_s, power in = power out.
  • Losses: flux leakage, winding resistance, eddy currents (laminated core), hysteresis.
  • Stepping up the voltage for transmission cuts the I²R loss by the square of the turns ratio.

Check your understanding

  1. 1. A transformer has 100 turns in the primary and 500 turns in the secondary. A 220 V supply is applied to the primary. What is the secondary voltage (ideal transformer)?

    1. 44 V
    2. 1100 V
    3. 220 V
    4. 11 000 V
    Show answer

    Answer: B. V_s = V_p × N_s/N_p = 220 × 500 ÷ 100 = 1100 V. It is a step-up transformer.

  2. 2. In an ideal step-down transformer with turns ratio N_p : N_s = 20 : 1, the primary current is 0.5 A. What is the secondary current?

    1. 0.025 A
    2. 20 A
    3. 10 A
    4. 40 A
    Show answer

    Answer: C. I_s/I_p = N_p/N_s = 20, so I_s = 20 × 0.5 = 10 A.

  3. 3. The core of a transformer is laminated in order to reduce

    1. eddy current losses
    2. flux leakage
    3. copper losses in the windings
    4. the turns ratio
    Show answer

    Answer: A. Thin insulated laminations break up the paths of the circulating (eddy) currents induced in the iron core, reducing the heating they cause.

  4. 4. Why does a transformer not work with a steady dc supply?

    1. The core would melt
    2. The primary resistance becomes infinite
    3. dc cannot magnetise iron
    4. A steady current gives a constant flux, so no emf is induced in the secondary
    Show answer

    Answer: D. Induction needs a changing flux. A steady current in the primary produces a constant flux in the core, so dφ/dt = 0 and the secondary gets no emf.

  5. 5. Assertion (A): A step-up transformer increases the voltage without violating the conservation of energy. Reason (R): In a step-up transformer, the current in the secondary is smaller than that in the primary in the same proportion.

    1. Both A and R are true, and R is the correct explanation of A
    2. Both A and R are true, but R is not the correct explanation of A
    3. A is true, but R is false
    4. A is false, but R is true
    Show answer

    Answer: A. Both are true. Since V_sI_s = V_pI_p (ideally), raising V by the turns ratio lowers I by the same ratio, so power is not increased. R explains A.