Producing induced emf, AC generators and transformers
List the three ways to change flux, show energy conservation for a sliding rod, derive ε = NBAω sin ωt, describe single-phase and three-phase alternators, and work with transformers and power transmission.
If something looks wrong, please tell us.
By the end of this lesson you can
- Name the three ways of changing flux: change B, change A, change orientation θ.
- Show that the mechanical power to move a sliding rod equals the Joule heating, B²l²v²/R.
- Derive ε = ε_m sin ωt with ε_m = NBAω for a coil rotating in a field.
- Describe the construction of an alternator and the 120° phase difference in a three-phase alternator.
- Use Vs/Vp = Ns/Np = Ip/Is, transformer efficiency, and explain why power is transmitted at high voltage.
Emf is not a force: it is the work done in taking unit charge round a circuit, measured in J C⁻¹ or volt. Cells, thermoelectric devices, solar cells and generators all provide emf, and generators are by far the most powerful. Since ε = d(BA cos θ)/dt in magnitude, there are exactly three ways to make an emf by induction.
Three ways to change the flux Φ_B = BA cos θ
-
Change B
- Relative motion of magnet and coil
- Changing current in a nearby coil
-
Change A
- Rod sliding on a fixed frame
- Motional emf ε = Blv
-
Change θ
- Rotate a coil in a field
- Or rotate the field inside a fixed coil
- Gives alternating emf
Changing the area: sliding rod and energy conservation
A rod of length l slides with velocity v on a fixed rectangular frame, in a uniform field B perpendicular to the frame. In time dt the enclosed area changes by l v dt, so dΦ_B = Blv dt and ε = Blv. If the loop's resistance is R, the current is i = Blv/R. This current-carrying rod feels a magnetic force F = ilB opposing its motion. To keep v constant, an equal force must be applied, and the mechanical power is P = Fv = ilBv = B²l²v²/R. The Joule heating is P = i²R = (Blv/R)²R = B²l²v²/R, exactly the same. Mechanical energy becomes electrical energy and then heat: energy is conserved.
Worked example 1: power balance for a sliding rod
B = 0.50 T, l = 0.40 m, v = 5.0 m s⁻¹, R = 2.0 Ω. ε = Blv = 0.50 × 0.40 × 5.0 = 1.0 V. i = 1.0/2.0 = 0.50 A. Opposing force F = ilB = 0.50 × 0.40 × 0.50 = 0.10 N. Mechanical power Fv = 0.10 × 5.0 = 0.50 W. Heating i²R = 0.25 × 2.0 = 0.50 W. The two agree.
Changing the orientation: alternating emf
A rectangular coil of N turns and area A rotates with constant angular velocity ω about an axis perpendicular to a uniform field B. At t = 0 its plane is perpendicular to B, so the flux linkage is a maximum, NBA. After time t it has turned through θ = ωt, and only the component of B normal to the coil, B cos ωt, links it: NΦ_B = NBA cos ωt. Then ε = −d(NΦ_B)/dt = NBAω sin ωt. The maximum value ε_m = NBAω occurs when sin ωt = 1, that is when the plane of the coil is parallel to the field. So ε = ε_m sin ωt: a sinusoidal (alternating) emf, and in a closed circuit it drives an alternating current i = I_m sin ωt.
ε = ε_m sin ωt, with ε_m = NBAω = NBA(2πf). Zero when the coil's plane is perpendicular to B; maximum when it is parallel to B.
Worked example 2: emf of a rotating coil
A coil of 200 turns and area 0.012 m² rotates at 50 revolutions per second about an axis perpendicular to a 0.25 T field. Step 1: ω = 2πf = 2 × 3.1416 × 50 = 314.2 rad s⁻¹. Step 2: ε_m = NBAω = 200 × 0.25 × 0.012 × 314.2 = 0.60 × 314.2 = 188.5 V. Step 3: when the coil has turned 30° from the position where its plane is perpendicular to the field, ε = 188.5 × sin 30° = 94.2 V. Step 4: when its plane is perpendicular to the field, ε = 0.
The AC generator (alternator)
An AC generator or alternator converts the mechanical energy used to rotate a coil or a field magnet into electrical energy, on the principle of electromagnetic induction. Small generators rotate the coil in a field; large ones, such as those in power stations, rotate the field inside fixed coils.
- Stator (stationary): a hollow, laminated iron or steel-alloy core with slots on its inner surface, holding the armature winding.
- Rotor (rotating): carries the field windings, magnetised by a DC source. The DC reaches them through slip rings on the shaft and brushes that slide on the rings.
Why a stationary armature and rotating field? The output current is taken straight from fixed terminals without brushes; insulating a fixed winding is easier; fewer sliding contacts are needed, and those carry only low-voltage DC; and the armature can be built rigidly to resist mechanical stress.
Single-phase alternator. Picture one rectangular loop PQRS fixed on the stator and a field magnet turning clockwise inside it. When the field is perpendicular to the loop's plane, the emf is zero; after 90° the field is parallel to the plane, the emfs in PQ and RS add, and the emf is a maximum; at 180° it is zero again; at 270° it is a maximum in the reverse direction (current along SRQP); at 360° it returns to zero. One rotation of the magnet gives one cycle of alternating emf. (Relative to clockwise-rotating poles, the conductor appears to move anticlockwise, which matters when you apply Fleming's rule.)
Three-phase alternator. The armature core has 6 slots 60° apart. Conductors 1 and 4 form coil 1, 3 and 6 form coil 2, and 5 and 2 form coil 3, so the three coils are 120° apart. As the field rotates, coil 2's emf starts its cycle 120° after coil 1's, and coil 3's 240° after. The three emfs differ in phase by 120°. An alternator with more than one coil is a poly-phase generator (two coils: two-phase).
Advantages of three-phase: for the same size it gives more power than a single-phase machine; for the same capacity it is smaller; and three-phase transmission is cheaper, since relatively thinner wires are enough.
The transformer
A transformer is a stationary device that transfers AC power from one circuit to another without changing its frequency, raising the voltage while lowering the current (step-up) or the reverse (step-down). Principle: mutual induction. Construction: primary and secondary coils with high mutual inductance on one laminated core of a good magnetic material such as silicon steel; the coils are insulated electrically but linked magnetically; the assembly sits in a container of insulating, cooling medium.
Working. AC in the primary sets up an alternating flux in the core. With no leakage, the same flux links every turn of both coils, so the rate of change of flux per turn, dΦ_B/dt, is common. The back emf of the primary equals the applied voltage: v_p = −N_p dΦ_B/dt. With the secondary open, v_s = −N_s dΦ_B/dt. Dividing, v_s/v_p = N_s/N_p = K, the transformation ratio. For an ideal transformer, input power v_p i_p equals output power v_s i_s, so v_s/v_p = N_s/N_p = i_p/i_s. K > 1: step-up (V_s > V_p, I_s < I_p). K < 1: step-down.
Efficiency η = (output power / input power) × 100%. According to the textbook, transformers are 96-99% efficient, higher than rotating machines because they have no moving parts.
| Loss | Cause | Reduced by |
|---|---|---|
| Hysteresis loss (core loss) | Core is magnetised and demagnetised every cycle | Steel of high silicon content |
| Eddy current loss (core loss) | Alternating flux induces eddy currents in the core | Very thin laminations |
| Copper loss | Joule heating i²R in the windings | Wires of larger diameter |
| Flux leakage | Not all primary flux links the secondary | Winding the coils one over the other |
Worked example 3: designing a step-down transformer
An ideal transformer works from 230 V and must give 12 V. Its primary has 1150 turns. Find the secondary turns, and the primary current when the secondary delivers 2.3 A. Step 1: N_s = N_p × V_s/V_p = 1150 × 12/230 = 60 turns. Step 2: output power = 12 × 2.3 = 27.6 W = input power. Step 3: I_p = 27.6/230 = 0.12 A. (Check with the ratio: I_p = I_s × N_s/N_p = 2.3 × 60/1150 = 0.12 A.)
Worked example 4: efficiency
A transformer takes 500 W and delivers 480 W. η = (480/500) × 100% = 96%. The remaining 20 W is lost as heat in the core and windings.
Why AC is transmitted at high voltage
Power stations (thermal, hydroelectric, nuclear) are often far from cities, and a sizeable part of the power can be lost as Joule heat I²R in long lines. Lowering R needs thicker copper or aluminium wire, which is costly. The better way is to lower the current: for the same power P = VI, a higher voltage means a smaller current. So the voltage is stepped up at the station, transmitted, and stepped down near the consumers. This is possible only because AC can be transformed.
Worked example 5: comparing transmission losses
A station sends 1.0 MW through lines of total resistance 10 Ω. At 20 kV: I = P/V = 1.0 × 10⁶ / 2.0 × 10⁴ = 50 A; loss = I²R = 2500 × 10 = 25 000 W = 25 kW, which is 2.5% of the power. At 200 kV: I = 5.0 A; loss = 25 × 10 = 250 W, only 0.025%. Raising the voltage 10 times cut the current 10 times and the loss 100 times.
Key takeaways
- Induced emf can be produced by changing B, A or θ; for a sliding rod the mechanical power equals the heat produced.
- A coil rotating in a field gives ε = NBAω sin ωt, maximum when its plane is parallel to B.
- Large alternators have a stationary armature (stator) and a rotating DC-fed field (rotor); three-phase emfs are 120° apart.
- Transformer: V_s/V_p = N_s/N_p = I_p/I_s; losses are hysteresis, eddy current, copper and flux leakage.
- High-voltage transmission lowers the current and so the I²R loss.
Check your understanding
-
1. A coil rotates uniformly in a uniform magnetic field. The induced emf is greatest at the instant when:
- the flux linked with it is greatest
- the plane of the coil is perpendicular to the field
- the coil is at rest
- the plane of the coil is parallel to the field
Show answer
Answer: D. ε = NBAω sin ωt, measured from the position where the plane is perpendicular to B. It is largest at ωt = 90°, when the plane is parallel to B and the flux is momentarily zero but changing fastest.
-
2. In a three-phase alternator, the emfs of the three coils differ in phase by:
- 60°
- 120°
- 90°
- 180°
Show answer
Answer: B. The three coils are placed 120° apart round the stator, so each emf begins its cycle 120° after the previous one.
-
3. An ideal transformer has 2000 primary turns and 100 secondary turns. If 240 V AC is applied to the primary, the secondary voltage is:
- 4800 V
- 24 V
- 12 V
- 2.4 V
Show answer
Answer: C. V_s = V_p × N_s/N_p = 240 × 100/2000 = 12 V. It is a step-down transformer.
-
4. Copper loss in a transformer is reduced by:
- using wires of larger diameter
- laminating the core
- using silicon steel for the core
- winding the coils one over the other
Show answer
Answer: A. Copper loss is i²R heating in the windings; thicker wire has less resistance. Laminations cut eddy current loss, silicon steel cuts hysteresis loss, and overlapping windings cut flux leakage.
-
5. The same power is sent along the same line, but the transmission voltage is raised 10 times. The power lost in the line becomes:
- 10 times smaller
- 10 times larger
- 100 times smaller
- unchanged
Show answer
Answer: C. I = P/V falls 10 times, and the loss I²R depends on I², so it falls 10² = 100 times.