- Practice
- About 15 min
- 5 practice questions
Storage and off-grid sizing: batteries, autonomy and array size
Convert battery ratings to energy, apply depth of discharge, size storage for days of autonomy, wire batteries in series and parallel, and size a small solar array for a daily load.
If something looks wrong, please tell us.
Solar and wind do not follow demand, so storage appears in many practice questions, especially on small off-grid systems such as a rural home or a village pump. The calculations are short, but they punish unit slips. Every load and price in this lesson is an illustrative value for practice. Work through the steps in order: energy of the battery, usable share, hours of supply, then array size.
Battery energy and usable energy
A battery is rated by voltage and by charge capacity in ampere-hours (Ah). Multiplying them gives the stored energy in watt-hours: Wh = V × Ah. Not all of it should be used, because deep discharge shortens a battery's life. The depth of discharge (DoD) is the share you are allowed to use, so usable energy = stored energy × DoD. The hours of supply then equal the usable energy divided by the load power.
Wh = V × Ah. Usable energy = Wh × DoD. Hours = usable Wh ÷ load W. Storage needed = daily load × days of autonomy ÷ DoD.
Series and parallel
Joining batteries in series adds their voltages and keeps the ampere-hours of one battery. Joining them in parallel keeps the voltage and adds the ampere-hours. Either way the total energy is simply the sum of the energies of the batteries, so two identical batteries always store twice as much as one.
Power rating versus energy capacity
A storage system has two separate ratings. Its power rating in kW says how fast it can deliver energy; its capacity in kWh says how much it holds. The time it can supply at full power is capacity divided by power. A 50 kW unit holding 200 kWh can supply full power for 4 hours. Exam traps often swap the two ratings, so read which unit each number carries.
Worked example 1: hours of supply
A 12 V, 100 Ah battery stores 12 × 100 = 1,200 Wh. With a depth of discharge of 50%, usable energy is 600 Wh. A 150 W load can therefore run for 600 ÷ 150 = 4 hours. If the battery were joined in series with an identical one, the voltage would be 24 V with 100 Ah, so the energy would be 2,400 Wh and the 150 W load could run for twice as long, with 50% DoD, 8 hours.
Worked example 2: storage for days of autonomy
A home uses 3 kWh a day and wants 2 days of supply with no sun. Take the permitted depth of discharge as 50%. Storage needed = 3 × 2 ÷ 0.5 = 12 kWh. On a 24 V system that is 12,000 ÷ 24 = 500 Ah. Dividing by the depth of discharge is the step most often forgotten: it reflects that only half of the bank may be used.
Worked example 3: sizing the array
The same home needs 3 kWh a day. Take 5 peak sun hours and an overall system efficiency of 0.75 for panels, wiring, battery and inverter (illustrative). Array rating = 3 ÷ (5 × 0.75) = 0.8 kW, or 800 W. With 400 W panels, two panels are needed. A cloudy-season design would use fewer peak sun hours, which raises the array size.
Types of storage in statement questions
- Batteries store electrical energy chemically and suit homes and small grids.
- Pumped storage lifts water to a higher reservoir and suits large grids.
- Molten salt stores heat in concentrated solar thermal plants.
- Hydrogen made by electrolysis stores energy in a chemical form that can be used later.
- A reservoir behind a hydro dam is storage too, since water can be released on demand.
Key takeaways
Battery energy is voltage times ampere-hours. Apply depth of discharge to get usable energy, and divide by it when sizing. Series adds voltage, parallel adds ampere-hours, and the energy always adds. Keep kW and kWh apart, and size the array from the daily load, the peak sun hours and the overall efficiency.
Check your understanding
-
1. How much energy does a 24 V, 200 Ah battery store?
- 8.3 kWh
- 48 kWh
- 4.8 kWh
- 0.48 kWh
Show answer
Answer: C. Energy = 24 × 200 = 4,800 Wh = 4.8 kWh. The value 8.3 comes from dividing 200 by 24.
-
2. Two identical 12 V, 150 Ah batteries are joined in series. What does the pair provide?
- 24 V and 150 Ah
- 12 V and 300 Ah
- 24 V and 300 Ah
- 12 V and 150 Ah
Show answer
Answer: A. Series adds voltages and keeps the ampere-hours of one battery, so 24 V and 150 Ah. The stored energy is 3.6 kWh, twice that of one battery.
-
3. A 5 kWh battery may be discharged to a depth of 60%. For how long can it run a 500 W load?
- 10 hours
- 3 hours
- 5 hours
- 6 hours
Show answer
Answer: D. Usable energy = 5 × 0.60 = 3 kWh = 3,000 Wh. Hours = 3,000 ÷ 500 = 6.
-
4. A load of 2 kWh a day needs 3 days of autonomy with a permitted depth of discharge of 50%. What storage is required?
- 6 kWh
- 12 kWh
- 3 kWh
- 1.33 kWh
Show answer
Answer: B. Storage = 2 × 3 ÷ 0.5 = 12 kWh. Without dividing by the depth of discharge the answer would be 6 kWh, which is the trap.
-
5. A storage unit is rated 50 kW and 200 kWh. For how long can it supply its full power?
- 4 hours
- 0.25 hours
- 10,000 hours
- 150 hours
Show answer
Answer: A. Time = capacity ÷ power = 200 kWh ÷ 50 kW = 4 hours. Dividing the other way gives 0.25, a unit trap.
Sign in to keep track of the lessons you finish.